AVEVA System Platform Does Not Support Unsigned Integers

AVEVA System Platform Does Not Support Unsigned Integers

The DDESuiteLink protocol in AVEVA System Platform 2020 R2 SP1 that connects to the OI Gateway R3, does not support unsigned 32 bit integers. All Integer datatype attributes on objects, are read as signed integers, despite being read correctly from the OPC UA server in the PLC. The solution is to never use bit 31